Booth #5036
© 2001-2008
AESYS Technologies, LLC

Series 400C
4SF-FSHS/BHP (.037m²- FSHS/kW)

Packaged firetube boiler assemblies incorporating three- and four-pass, centerline furnace, down-draft, dry-back technology and rated at nominal 4SF-FSHS/BHP (.037m² - FSHS/kW). Capacities available from 30 to 1,300 BHP (294 to 12,743 kW) at standard design pressures of 15 to 300 PSIG (103 to 2,068 kPa).

Due to its economical and compact profile, the Y-SG Series 400C is particularly suited for continuous operation where stable process and space heating load demands are available. Moderate furnace heat release rates assure reduced vessel stress and thermal NOx production. Centerline furnace accommodates uniform vessel stress.

Series 400C S3D/S4D H3D/H4D H3D/H4D
Standard Safety, Operation and Level Control Devices S050 to S300 S015 W030 to W160
Pressure Gauge
Temperature Gauge N/A N/A
Float-Type LWCO - Pump Control
w/ Gauge Glass Assembly
N/A
Probe-Type LWCO - Manual Reset
High-Pressure Limit Control - Manual Reset •†
Operating Pressure Limit Control •†
Firing Rate Pressure Control •†
Low-Fire Hold Pressure Control •† •†
Minimum Water Temperature Control N/A N/A •†
ASME Safety Valve(s) N/A
ASME Safety Relief Valve(s) N/A N/A
Single-Point Spring-Loaded Furnace Pressure Relief Device
† Temperature Limit Control
Download Dry-Back Firetube Boiler Literature
High pressure steam boilers are constructed in accordance with ASME Section I ‘Rules for Construction of Power Boilers’ at standard design pressures of 50 to 300 PSIG (344 to 2068 kPa). For design pressure beyond standard offering, please consult factory.
Low pressure steam and hot water boilers are constructed in accordance with ASME Section IV ‘Rules for Construction of Heating Boilers’ limited to design steam pressure of 15 PSIG (103 kPa) and reverse flow hot water service of 30 to 160 PSIG (206 to 1103 kPa) – maximum 250°F (121°C).